Features & Benefits:
- Fiber optic (multi-mode and/or single-mode fiber), wire, or combination wire/fiber communications path
- NFPA Style 4 or Style 7 network operation
- Based on peer-to-peer network architecture
- High-speed data communications—40% faster than NOTI-FIRE-NET (12Mb for wire, 100 Mb for fiber)
- Supports all ONYX® Series Fire Alarm Control Panels
- Supports NWS, FirstVisionTM, BACnet and Modus, CAP, VESDA-HLI, SLC-IM and LED Sign Gateway applications
- Increased network node capacity to 200 nodes for large applications
Specifications
- 2 Node Addresses per network card
- Network control-by-event
- Inherently regenerative system. Each node acts as a repeater to reshape and regenerate data signals
Compatibility:
- NFS-3030/NFS2-3030
- NFS-640/NFS2-640
- NFS-320
- NCA/NCA-2
Wire Specifications:
- Distance: 3000 feet
- Gauge: 14-18 AWG
- Configuration: Point-to-Point Bus
Fiber (Multimode) Specifications:
- 62.5/125µm: 10 dB limit
- 50.0/125µm: 6.5 dB limit
- Wavelength: 1310nm
- Fiber Connector Style: LC
Fiber (Single mode) Specifications:
- 9.0/125µm: 30 dB limit
- Wavelength: 1310nm
- Fiber Connector Style: LC
Listings:
- UL/ULC Listed: S635 (HS-NCM, Printer), S5526 (ONYXWorks)
- FM Approved (HS-NCM)
- CSFM: 7300-0028:0257 (HS-NCM), 7300-1525:0103:0103 (ONYXWorks)
- FDNY: COA #6022 (HS-NCM), COA #6041 (ONYXWorks)
Reviews