Features & Benefits:
- Capable of two modes of operation: Firefighter’s Smoke Control Station (FSCS) or Heating, Ventilation, and Air Conditioning (HVAC)
- Communication to the SCS is accomplished over a two-wire serial interface employing an EIA-485 communication standard
- Eight independent switch groups as well, however, since the SCS-8L/SCE-8L is a lamp driver version of the SCS-8/SCE-8 each switch group consists of contacts for connection of a three-position switch and contacts for connection of three lamps or LEDs
Specifications
- Power for the SCS is provided via a separate 24 VDC regulate power loop. If power is lost, a trouble signal will result at the control panel
- Each SCS has two rotary decimal switches for addressing and eight dipswitches for mode configuration
- Only one SCE can be used for each SCS and a maximum of 32 pairs can be used with each NOTIFIER control panel
- The system has the capability to control and monitor 512 separate AHU fans or dampers
Listings:
- UL Listed: file S5511
- ULC Listed: file CS100
- CSFM approved: file 7300-0028:183 (SCS-8, SCE-8 only)
- MEA approved: 289-91-E8